24 starpac 3 pressure sensor troubleshooting – Flowserve StarPac 3 User Manual

Page 56

Advertising
background image

StarPac Intelligent Control System FCD VLENIM0066-05 04/14

56

®

24 StarPac 3 Pressure Sensor Troubleshooting

Figure 28: StarPac 3 Pressure Sensor Troubleshooting Chart

Pressure reading

is incorrect

Is pressure

slightly off or

saturated?

Saturated

Is reading

saturated

low or high?

Low

Slightly

off

Recalibrate

sensor

Make sure

sensor is

plugged in

Yes

Is sensor

working?

No

Swap sensors

Yes

No

Same problem

appear?

Problem is in

wiring or board

Contact Factory

Replace

sensor

Replace

sensor

Check wire harness

for shorts or

contamination

Replace bad

O-rings

Tighten all

fittings

Check fittings

and O-rings

Yes

Is reading

correct?

No

Yes

No

Does reading

return to full

scale?

Reconnect

sensor

Yes

No

Does reading

go to 0?

Disconnect

sensor

High

Clean contacts

Advertising