StarPac Intelligent Control System FCD VLENIM0066-05 04/14

flowserve.com

®

Figure 22: Driver Module Vent

Maximum Allowable

Driver Housing

Back Pressure

2.0 psig (0.14 barg)

1/4” NPT x 1/4”

Swagelok Tube Fitting

1/4” FNPT x 1/8”

NPT Reducer

The spool valve chamber (see Figure 23) must also be vented through the spool valve cover. Install a tube fitting into
the spool valve cover (part no. 179477). Connect the necessary tubing/piping to this fitting to route the exhausted na-
tural gas to a safe environment. The maximum allowable back pressure in the spool valve chamber is 8 psig (.55 barg).
Pressures greater than 8 psig will cause vented gas to leak past the spool cover O-ring to the atmosphere and will result
in overshoot of the positioner.

Figure 23: Spool Cover Vent

3/8” NPT x 3/8” Swagelok

Tube Fitting

Maximum Allowable

Spool Back Pressure

8 psig (0.55 barg)

Customer Connection

3/8” Tubing