StarPac Intelligent Control System FCD VLENIM0066-05 04/14

28

®

release the locking sleeve of the Lemo™ connector by moving the collar away
from the sensor and disconnect the connector from the sensor. Swing the sen-
sor conduit out of the way (refer to Figure 10).

Figure 10: Disconnecting Lemo

TM

Connector

4. Unscrew the sensor from the sensor boss.

5. Remove the sensor O-ring or gasket and replace with a new one. Make sure

the environmental O-ring seal is in good condition and in place on the new
sensor.

6. Install the new sensor into the sensor port making sure the O-ring or gasket

remains properly in place while tightening the sensor. Tighten the sensor until
it seats metal-to-metal at the gasket section of the sensor port, ensuring the
proper compression of the process O-ring or gasket seal.

7. Plug the pressure sensor cable connector into the pressure sensor. Align the

red dots on the sensor and connector to reconnect the Lemo™ connector to
the pressure sensor. Fully seat the connector until the locking sleeve latches.
Replace the sensor nut and tighten.

8. Pressurize the valve body to make sure the sensors are properly seated before

attaching the sensor conduit and tightening.

9. Reattach the conduit lines and securely tighten the fittings.