ONICON F-5100 Insertion User Manual

Page 19

Advertising
background image

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]

F-5100 Insertion Thermal Mass Flow Meter Manual 05/15 - 0663-20 / 18333

Page 19

3.5.1 Analog Output

The F-5100 is provided with a single 4-20 mA output for instantaneous rate. This output is

electrically isolated from earth, but shares common with the scaled pulse output and, on

DC versions of the sensor, with input power.

The output is programmed at the factory. Refer to the attached laminated tag or the

certificate of calibration for information regarding the programmed full scale flow.

Contact ONICON for assistance if the full scale flow rate requires reprogramming.

3.5.2 Pulse Output

The F-5100 is provided with a single scaled pulse output for totalizing. This is an active

pulse output with a nominal pulse amplitude of 24 VDC (12 VDC for 12 V versions of the

sensor). In all versions, the pulse duration is 500ms.

This DC pulse output is electrically isolated from earth, but shares common with the

analog output and, on DC versions of the sensor, with input power. This output is

programmed at the factory. Refer to the attached laminated tag or the certificate of

calibration for information regarding the programmed pulse value.

Contact ONICON for assistance if the scaled pulse output requires reprogramming.

CAUTION

Cable glands shipped with the sensor are for shipping purposes only. Remove and replace with

approved glands when installing the sensor.

!

WARNING

If the sensor is being installed in a Class 1 hazardous location, the installation must comply with

all appropriate electrical codes.

!

WARNING

The sensor must be connected to a protective earth wire at the transmitter and at the sensor for

remote mount sensors as per electrical codes.

!

3.5 ELECTRICAL INSTALLATION

The electrical installation of this product must comply with all federal, state and local building

codes. Connect and re-verify all output signal and safety earth wiring connections prior to

connecting power.

All connections must be made through the (2) ½’ NPT cable glands located on the enclosure.

To access the terminal wiring connections, remove the rear cover from the enclosure.

IMPORTANT NOTICE

The nominal pulse output voltage from this sensor is 24 VDC. A pulse isolator module has been

provided with this sensor that will convert this active pulse into an isolated dry contact output.

Refer to section 3.5.4 Using the Pulse Isolator Module for details.

i