F-5100 Insertion Thermal Mass Flow Meter Manual 05/15 - 0663-20 / 18333

Page 26

SECTION 5.0: TROUBLESHOOTING GUIDE

NOTE: Also refer to the START-UP AND COMMISSIONING GUIDE located on page 24.

REPORTED PROBLEM

POSSIBLE SOLUTIONS

No signal

• Verify that the sensor is properly inserted into the pipe.
• Verify that the electronics enclosure is parallel with the pipe.
• Verify supply voltage.
• Verify correct wiring to control system (see wiring diagram).
• Verify that there is flow in the pipe.
• Please contact ONICON for further assistance.

Reading is too high or
low

• Verify pipe size. Contact ONICON if pipe size is different from that

shown on the sensor tag.

• Verify that the sensor is properly inserted into the pipe.
• Verify that the electronics enclosure is parallel with the pipe.
• Verify correct wiring to control system (see wiring diagram).
• Confirm that the control system is programmed for correct flow range

or pulse scale factor.

• Verify that the sensor cable shield is connected to earth at the control

system. Lack of proper shielding can lead to excessive noise that can
affect the flow reading.

• Verify that the sensor is connected to earth.
• Check for ground loop or offset voltage: Disconnect analog signal

input from control system and measure analog output directly from
the flow sensor. Reconnect signal input to control system and measure
the analog signal again. Any difference between these readings
indicates a potential ground loop or offset voltage.

• Sensor may be contaminated. Remove sensor from pipe and wipe off

or clean with mild detergent and water.

• Sensor is being used to measure flow of a different gas or gas mix than

the sensor was specified and calibrated for.

• Please contact ONICON for further assistance.

Erratic readings

• Confirm that the sensor is connected to earth and all cabling is

properly shielded.

• Please contact ONICON for further assistance.