Loss in heating and cooling output

Depending on the length of the refrigerant piping and the difference in elevation between the indoor and out-

door units, there may be a loss in heating or cooling output. These can be calculated using the following dia-

grams.

Loss in heating output WKF/WKF-compact 85

25

30

15

20

10

5
0

-5

-10
-15
-20
-25
-30

0

5

10

15

20

25

30

35

40

45

50

A

B

[m]

[m]

100%

99%

97%

95%

95%

95%

95%

92%

92%

92%

+30 m

0 m

-30 m

Fig. 25: Loss in heating output WKF/WKF-compact 85

A: Difference in elevation

B: Length of refrigerant piping

Loss in cooling output WKF/WKF-compact 85

25

30

15

20

10

5
0

-5

-10
-15
-20
-25
-30

0

5

10

15

20

25

30

35

40

45

50

A

B

[m]

[m]

100%

98%

95%

95%

90%

90%

90%

87%

87%

87%

+30 m

0 m

-30 m

Fig. 26: Loss in cooling output WKF/WKF-compact 85

A: Difference in elevation

B: Length of refrigerant piping