REMKO WKF 85 User Manual

Page 77

Advertising
background image

Messages, warnings and errors displayed on the SmartControl

Messages

ID

Description

Details

6000

Storage tank 1: Max.

temperature reached

The temperature on one of the probes in storage tank 1 is higher than the

maximum permitted

6001

DHW preparation

There is no active requirement to charge the storage tank.

6002

Heat pump compressor

start

Heat pump compressor start

6005

Internal pump lead time The internal pump runs at a reduced speed during the pump lead time.

6006

Switching cycle disa-

bled

The heat pump was disabled in order to reduce the compressor's

switching cycles.

6007

Min. holding time

The heat pump is disabled due to a minimum holding time.

6008

Disable signal S16

The heat pump is disabled due to a disable signal.

6020

Internal pump after-run

time

The internal pump runs at a reduced speed during the pump after-run

time.

6105

Defrost heat pump

Defrost heat pump

6107

Anti-freeze protection

active

Anti-freeze protection active

6108

Random delay after

power failure

Random delay after power failure (up to 200 seconds after power returns)

- the purpose of the

6109

Outdoor temp. Heat

pump usable limit

Outdoor temp. Heat pump usable limit - the heat pump is disabled due to

the usable limits being

6111

Heat pump bivalence

temperature

Heat pump bivalence temperature - the heat pump is disabled because

the temperature has

6113

Solar heating

Solar heating - heat generators are disabled

Warnings

ID

Description

Details

8102

Temperature discrep-

ancy in solar cycle

The collector temperature is at least 60K higher than the storage tank

temperature.

8103

Overnight collector

temperature

A collector temperature of at least 45 °C (113 °F) occurred overnight.

8107

Compressor status

The active operating mode is safety mode because the compressor is

active without demand.

8132

Anti-freeze protection

active

The anti-freeze protection function is currently active - check the room cli-

mate mode set.

8138

HW storage tank set

temp.

The hot water storage tank set temperature was reduced due to low out-

side temperatures.

8139

Lower application area

(heating)

The temperature has currently dropped below the guaranteed application

area of the external

8140

Upper application area

(heating)

The guaranteed application area of the external unit in heating mode is

currently exceeded.

77

Advertising
This manual is related to the following products: