The stop cocks supplied are to be positioned

directly at the connections for the heat pump

for the heater circuit inlet and return lines. The

shut-off valves each contain a thermometer.

Fig. 50: Shut-off valves

Turning the thermometer heads serves to close

or open the stop valves! The dial be brought

into the desired position.

n

Install the dirt traps delivered with the unit out-

side the heat pump in the return line. Ensure

that the dirt trap remains accessible for inspec-

tion.

n

Be sure to position one gate valve upstream

and another downstream of the dirt traps. This

ensures that the dirt traps can be checked at

any time without loosing water.

n

The dirt traps must be checked during every

service of the system.

n

Additionally, a hand-operated bleeder is

installed on the heat pump for additional

bleeding.

n

All visible metallic surfaces must be addition-

ally insulated.

n

Cooling mode via the heating circuit requires a

completely vapour diffusion tight insulation

along the entire length of the pipework.

n

All outgoing heating circuits, including the con-

nections for water heating, are to be secured

against circulating water by means of check

valves.

n

Before being placed in service, the system

must be thoroughly flushed. Conduct a seal

test and perform a thorough bleeding of both

the indoor unit and the entire system - repeat-

edly, if necessary.

Actual schemas for hydraulic integration can

be found on the internet at www.remko.de