REMKO WKF 85 User Manual

Page 43

Advertising
background image

Minimum distances in mm for the outdoor modules WKF/WKF-compact

1

2

3

4

5

6

>= 250

>= 1500

>= 1500

>= 250

>= 250

>= 300

>= 600

>= 600

>= 250

>= 1500

>= 2000

Fig. 45: Minimum distances for installation of an outdoor module in mm for WKF/WKF-compact

1:

Against a wall, free flow air forward, backward

flow restriction

2:

Against a wall, facing the wall air outlet, flow

front restriction

3:

Freely between two walls, facing the wall outlet,

Sides: flow restrictions in front and rear

4:

In a niche, free flow air to the front, rear and

flow restriction on both sides.

5:

Before a covered wall, free flow air to the front,

rear and top of flow restrictions

6:

Before a covered wall, air outlet towards wall,

flow restrictions behind and above

1

2

3

4

>= 1500

>= 300

>= 600

>= 600

>= 600

>= 250

>= 600

>= 600

>= 1500

>= 250

>= 1500

>= 3000

>= 600

>= 250

>= 3000

Fig. 46: Minimum distances for installation of several outdoor modules in mm for WKF/WKF-compact

1:

Against a wall, facing the wall air outlet, flow

front restriction

2:

In a niche, free flow air to the front, rear and

flow restriction on both sides.

3:

Between two walls, facing the wall outlet and

other modules, Sides: flow restrictions in front

and rear

4:

Between two walls, air outlet towards wall, or

the external modules-free: flow restriction in

front, rear and internal modules on the sides.

43