Page 57

Advertising
background image

n

Electrical protection for the system is imple-

mented in accordance with the information in

the technical data. Observe the required con-

ductor cross-sections!

n

All cables must be connected with the correct

polarity and strain relief.

n

Follow the connection schematic and the circuit

diagram.

n

Connect the two-wire control cable to terminals

F1, F2 and the earth terminal.

n

When connecting the control cable, make sure

that polarity is correct.

n

If the outdoor module is installed on a roof, it

and the supporting structure must be earthed

separately. (Connection to a lightning rod or a

concrete-footing earth electrode)

n

In the seriesWKF/WKF-compact 180 it must be

ensured that only the terminals L1(R), L2(S),

L3(T) and N are connected. (see Fig. 61).

2

3

1

Fig. 59: Connection terminals - outdoor module

WKF/WKF-compact 85

1: Display

2: Power supply 230V/1~ /50Hz

3: Control cable F1/F2

1

Fig. 60: Connection terminals - outdoor module

WKF/WKF-compact 120

1: Power supply 230V/1~ /50Hz

Fig. 61: Connection terminals - outdoor module

WKF/WKF-compact 180

NOTICE!

Make sure to connect the outdoor unit neutral

connector properly, otherwise the varistors on

the line-filter circuit board will be destroyed.

Temperature sensors

n

The number of sensors required can vary with

the type of system.

n

Observe the pertinent notes for the sensor

position found in the hydraulic schematic.

n

The standard model includes an external

sensor (S10), a submersible sensor (intended

for use as a custom hot-water sensor (S08)

and a sensor for a total inlet at the indoor

module.

57