REMKO WKF 85 User Manual

Page 31

Advertising
background image

Heat pump modes

Heat pumps can work in various operating modes.

Monovalent

The heat pump the only source of heat for a

building all year round. This mode is particularly

suitable for heating plants with low supply-water

temperatures and is primarily used in combination

with brine/water and water/water heat pumps.

Single energy source

The heat pump has an E-heater to handle peak

loads. The heat pump covers the majority of the

required heating power. Occasionally, when it is

extremely cold outside, an electrical booster-

heating system switches on as required in order to

support the heat pump.

Bivalent parallel

The heat pump provides the entire heating energy

down to a predetermined outdoor temperature. If

the temperature drops below this value, a second

heat source switches on to support the heat pump.

There is a distinction to be made here between

alternative operation with oil- or gas heat and

regenerative operations with solar energy or

wood-fired heating. This mode is possible for all

heating systems.

Layout

A precise calculation of the building's heating load

according to EN 12831 is required for the design

and dimensioning of a heating system. However,

approximate requirements can be determined

based on the year of construction and the type of

building. The table

Ä on page 32 shows the

approximate specific heating loads for a number of

building types. The required heating system output

can be calculated by multiplying the area to be

heated with the given values

For a precise calculation, various factors must be

considered. The transmission-heat requirement,

the infiltration heat-loss and an allowance for water

heating comprise the total heating output which the

heating system must provide.

The total area of the floor surfaces, exterior wall

windows, doors and roofing is required in order to

determine the transmission heat requirement. In

addition, information about the materials used in

the building is required, as these lead to extremely

varied thermal transmission coefficients (the so

called K value). Also required are the room temper-

ature and the standard outdoor temperature, that

is, the lowest outdoor-temperature on average that

will occur during the year. The equation for calcu-

lating the transmission-heat requirement is Q=A x

U x (t

R

-t

A

) and must be calculated separately for all

room-enclosure surfaces.

The infiltration heat requirement takes into consid-

eration how often the heated room air is

exchanged for cold external air. The room volume

(V), the air exchange frequency (n) and the spe-

cific heat capacity (c) of the air is also required in

addition to the room temperature and average low

temperature. The equation is: Q=V x n x c (t

R

-t

A

).

An approximate allowance for heating water - per

person according to VDI 2067: 0.2 kW

Example

A residential home comprised of 150 m² living-

space and a heat requirement of 80 W/m² has

been selected for the example design. A total of

five persons live in the house. The heat load

amount to 11.5 kW. Adding a drinking water allow-

ance of 0.2 kW results in a required heat capacity

of 12.5 kW. Depending on the power company, an

additional charge must then be made in order to

factor in the service time-out period. The rating and

determination of the heat pump's balance-point

temperature derives graphically from the heat

pump's temperature-specification heat-output dia-

gram. (In the example, 35 °C for a floor heating-

system). Next, the heat load for the standard out-

door temperature (the lowest temperature of the

year locally) and the heat threshold are marked on

the graph. The outdoor-temperature-dependent

heating requirement, simplified here as a straight-

line relationship between heat-load and the start of

the heating season, is recorded in the graph of

heat-load curves. The intersection of the two

straight lines with the rated heat-load curve is

plotted on the X axis, where the balance-point tem-

perature is read. (in the example, ca.-3°C) The

least load of the 2nd heat source is the difference

between heat load and the heat pump's maximum

heat output on these days. (In the example, the

capacity necessary to cover peak loads is ca. 3

kW.)

31

Advertising
This manual is related to the following products: