Fig. 43: Protection from wind

1: Wind

NOTICE!

The site for the outdoor unit must be selected

so that machinery noise that occurs disturbs

neither the residents nor the facility operator.

Observe the TA-noise specifications as well as

the table containing the drawings relating to

sound pressure levels.

20 cm

1

Fig. 44: Protection from snow

1: Snow

Point of emissions

Assessment level in accordance

with TA noise

days in dB(A)

nights in dB(A)

Industrial areas

70

70

Commercial areas

65

50

Core areas, village areas and mixed zones

60

45

General residential areas and small housing estates

55

40

Exclusively residential areas

50

35

Spa areas, hospitals and mental institutions

45

35

Isolated noise peaks of short duration may not exceed 30 dB(A) during the day and 20 dB(A) at night.

Definition of the Danger Area

WARNING!

Access to the unit is only permitted for author-

ised and trained persons. If unauthorised per-

sons can approach the danger areas, these

areas must be identified with corresponding

signs, barriers, etc.

n

The external danger area surrounds the equip-

ment up to a distance of 2 m, measured in all

directions from the unit housing.

n

The external danger area on-site can differ as

a result of the setup. The specialist company

performing the installation work bears the

responsibility for this.

n

The internal danger area is located inside the

machine and can only be reached with the use

of an appropriate tool. Access is prohibited for

unauthorised persons!