Space Ray PTS Series Single Stage User Manual

Page 42

Advertising
background image

Form 43343330
Aug 2012

-41-

In multiple heater applications

multiple heater applications

multiple heater applications

multiple heater applications, the combustion air intake may be ducted individually or common ducted in the

same configuration as shown for venting in Section 16.0). For combustion air intake duct sizing, please refer to
the Vent Sizing Table

Vent Sizing Table

Vent Sizing Table

Vent Sizing Table and use the diameter indicated, based on the number of heaters per duct.

Flue vent termination
must be 1 ft. (30 cm)
higher than combustion
air inlet cap.

Combustion
Air Intake

SIDE VIEW

(straight configuration)

Combustion Air Cap
(Leslie VersaCap
Type B)

4” Diameter
Single-Wall Pipe

Flashing

1/2” (12mm) fall per 20ft (6m)
toward vent terminal

Horizontal

Through Sidewall

6” (15cm)
Minimum

4” Starting Collar

Burner Box
(side view)

3 ft. (91cm)
Minimum

4” Flexible Air Inlet Hose
2 Ft. Long

(Part No. 30675020)

4” Spring
Tension Clamp (2 each)

(Part No. 30676040)

Vertical

Through the roof

Advertising
This manual is related to the following products: