Note: When the PTS / PTU is operated by a thermostat interrupting the line voltage (120V) to the heater then the
post purge function is disabled.

If the flame is not sensed during sequence T3 then the burner will automatically begin re-ignition sequence T2.
The ignition sequence will be repeated three times with a 60 second inter-purge. If the flame is not re-
established the heater will go to lockout.

20.0)

CONTROL COMPONENT LOCATION

Legend

:

1

Cabinet Assembly

2

Access Panel - Top

3

Access Panel - Hinged (2 ea)

4

Access Panel - LH Burner

5

Access Panel - RH Burner

6

Air Inlet Screen

7

Gas Inlet Connection - 1/2”NPT

8

Power Supply Cord - 120V

9

Burner Sight Glass

10

Indicator Light - Amber (Gas Valve)

11

Indicator Light - Red (Air Switch)

12

Tube Flange Connection

13

Main Burner

14

Flame Screen (200m/BTU units only)

15

Electrode

16

Flame Sensor

17

Main Burner Orifice

18

Air Restrictor Plate

2

9

4

3

6

7

8

10

11

5

12

25

Note: This panel
must remain closed
for burner operation.

Note: This panel
must remain closed
for burner operation.

30

3

32

24

1

26

27

28

29

32

14 15

16

13

17

18

19

22

23

20

33

21

34

31

19

Gas Control Valve

20

Ignition Module

21

Ignition Cable

22

Blower Assembly

23

Transformer - 120/24 VAC

24

Terminal Block/Fishpaper Shield

25

Air Switch

26

Air Sensing Tube (P1+)

27

Air Sensing Tube (P2-)

28

Manifold Pipe

29

Manifold Support Bracket/Clamp

30

Thermostat Connection Block

31

Terminal Bushing (TISS connection)

32

Starting Collar

33

Valve Holder Plate

34

Fuseholder/Fuse (2 amp)