0) troubleshooting guide – Space Ray PTS Series Single Stage User Manual

Page 46

Advertising
background image

Form 43343330
Aug 2012

-45-

22.0)

TROUBLESHOOTING GUIDE

No

Y

es

Are the blue wires

secure in the

terminals and firmly

on the ignition

module terminals?

Move orange wire to

NO terminal. Rest

art

troubleshooting.

Replace motor

.

Remove any

obstructions. Repeat

st

art up. If motor will

not run. replace

motor

.

No

Y

es

Disconnect the power

and check the blower

wheel. Does it turn

freely?

No

Y

es

During st

art up, is

there 120V between

ground and the IND

terminal on the

module?

Clean out hoses and

probes.

Switch hoses on the

pressure t

ap

s.

Check NO terminal of

the air switch

connection. Replace

red light.

No

Y

es

T

urn on line volt

age

and thermost

at. Does

the red monitoring

light come on?

No

Y

es

Does the blower

come on?

No

Y

es

Does the LED on the

ignition module flash

once?

No

Y

es

Is the black t

ap on the

air switch connected

to the upper probe?

Check the probes and

hoses to the air switch

are they clear and

unobstructed?

Replace air switch.

No

Y

es

Is 120V at the terminal

block in the blower?

Check line volt

age at

thermost

at and line

volt

age circuit. Rep

air

fault.

No

Y

es

Is there 120V

between ground and

the L1 terminal on the

module?

No

Y

es

Check terminals for

continuity and rep

air

.

No

Y

es

Is the LED on the

ignition module

steady ON?

No

Y

es

Is there 24V between

the inlet to the fuse

carrier and the

ground?

No

Y

es

Is there 24V on the

other side of the fuse

carrier?

No

Y

es

Is there 24V between

both terminals of the

TISS and ground?

No

Y

es

The

TISS has broken

continuity

. Check the

first tube and reflector

is there a hole?

Check

TISS wire for

a break if it is close to

the terminal rep

air

.

Otherwise replace

TISS wire.

Replace heat

exchanger tube,

reflector and

TISS.

No

Y

es

Is there 24V between

both terminals of the

thermost

at connection

and ground?

No

Y

es

Does the system have

a 24V individual

thermost

at?

No

Y

es

Is 120V at the terminal

block in the blower?

Check that red wire is

connected to

TH from

air switch terminal C.

Rep

air connection.

Replace ignition

modules.

Rep

air or replace

jumper check all wire

terminals.

Rep

air or replace

thermost

at. Check

external wiring.

Replace ignition

module.

Check terminals for

continuity at

transformer

. If they

are good, replace

transformer

.

if fuse carrier is tight

and the fuse has no

continuity

, replace the

fuse.

No

Y

es

Is the blower on?

No

Y

es

Does the LED on the

ignition module flash

once?

No

Y

es

Is the orange wire

from PSW connected

to the NO terminal of

the air switch?

No

Y

es

Are air switch

terminals jumpered?

Remove jumper

, air

switch must be open

circuit first for blower

to operate.

Air switch is stuck in

the closed position.

Replace air switch.

Move black light wire

to NO terminal of the

air switch. Rest

art the

troubleshooting.

No

Y

es

Does the amber light

come on?

No

Y

es

Is the LED on the

ignition module

steady ON?

No

Y

es

Af

ter 15 seconds

post purge is there

24V between V1 and

V2 ignition module

terminals?

Replace ignition

module.

Replace ignition

module.

Rep

air connection.

Rest

art

troubleshooting.

No

Y

es

Are the black wires

to the amber light

securely on the gas

valve terminals?

Rep

air connection.

Rest

art

troubleshooting.

Replace amber light.

Rest

art

troubleshooting.

T

roubleshooting

continued on the next

p

age.