eFlo Electronic Flow Meter Operations Manual

Super Systems Inc.

Page 9 of 25

Modbus Register

Number

Description

35

Auto (1) / Manual (0) for Control

36

(Not Used)

37

Reset Totalizer Values to Zero

38

(Not Used)

39

Totalizer Units (0 to 9999)

40

Totalizer in 10,000s (0 to 9999 -> 0 to 99,990,000)

41

Totalizer in 10,000,000s (0 to 9999 -> 0 to 999,900,000,000)

Table 4 - Modbus Registers and Descriptions

Operating Procedure

The eFlo system is equipped with a flow rate alarm (high and low), flow rate totalizer, and

integrated valve control. The unit can be operated in either manual or automatic mode for flow

rate control. This section of the manual provides an explanation of how the unit is operated:

valve control modes, flow limit control, flow alarming, flow totalizing, and programming of the

unit.


IMPORTANT!

For best long term results, it is recommended that pressure be maintained on the flow meter at

all times. Pressure can be maintained when the shut off solenoid/valve is downstream from the

outlet of the meter. This will ensure long term calibration and accuracy.


Figure 3 shows the layout of the flow control panel on the eFlo unit. An explanation of the

panel’s components is provided as well. The panel layout will be referenced further in this

section.