Run Indicator
The green

Run

LED lights when the PLC executes the program and operates normally.


Link Indicator
The

Link

indicator is not used.


Error Indicator
The red

Error

LED lights when an internal self-diagnosis detects an error and stops PLC

operation (the

Run

LED is off).


4-6 Level 1 Temperature Controller LED Indicators

888

Process Value Numeric LED

During normal operation, the process value LED on the controller displays the process
temperature at the

TO PROCESS

thermocouple. It also lists parameters during setup and error

messages if an error occurs. Press the

Mode key once to display the process temperature set

point.

ON

Output LED

The orange

On

Output LED lights when control output energizes the process air heater.

AL

Alarm LED — High Temperature Alarm

The

AL

alarm indicator lights when the process air temperature rises more than 25° from the set

point (factory default). The alarm relay in the PLC energizes when this LED lights. The
audible/visual alarm actuates if the dryer is so equipped. All heaters turn off and the blowers stay
on to cool the heaters. You can adjust the alarm value; see Section 6-5 on Page 43 for more
information.

Deviation Indicators

Arrow Up

The arrow up indicator lights when actual temperature is higher than the set point.

In Range

The in-range square indicator lights when temperature deviation is within plus or minus one
percent (±1%) of the set point.