MOBILE HOME INSTALLATION


Once you have properly marked the position of your unit and the
floor protection as outlined in the Residential Installation, secure it
to the floor using two lag bolts ⅜" x 3½" through the two holes in the
pedestal base or through the legs.
A supply of fresh air has to be supplied to your unit. Cut a minimum
3inch diameter hole through the wall using an elbow off the com-
bustion air duct to the outside. Use 3" duct with a mesh grill to pipe
fresh air into the combustion air intake of the appliance. For Mobile
Home units installed in the U.S. the unit must be grounded using a
#8 ground wire with approved termination and star washer.
In addition to standard installation instructions the following require-
ments are mandatory for installation in a mobile home.

1. The stove must be permanently bolted to the floor of the Mobile

Home using the floor screws provided.

2. The stove must have a permanent outside air source for com-

bustion connected to the outside air kit only.

3. The stove must be electrically grounded to the steel chassis of

the Mobile Home.

4. A listed double-wall connector & chimney system, roof thimble,

spark arrestor and roof flashing kit suitable for use in Mobile
Homes & this stove must be used.

5. The chimney shall extend at least 3 ft. (914mm) above the part

of the roof through which it passes. The top of the chimney
should project at least 2ft. (610mm) above the highest elevation
of any part of the Mobile Home within 10 ft. (3048mm) of the
chimney.

6. The chimney system shall comply with Local Requirements. Use

chimney meeting UL 103 HT in the USA or ULC S629 in Canada

WARNING! NEVER DRAW OUTSIDE COMBUSTION AIR FROM A WALL, FLOOR OR CEILING CAV-
ITY OR FROM ANY ENCLOSED SPACE SUCH AS A GARAGE, CARPORT OR UNDER A MOBILE
HOME.

CAUTION: THE STRUCTURAL INTEGRITY OF THE MOBILE HOME ROOF, FLOOR, WALLS AND
CEILING MUST BE MAINTAINED.

6. Check any other local building code as other local codes may apply.

WARNING: DO NOT INSTALL IN A SLEEPING ROOM OF A MOBILE HOME.

7. Maintain the integrity of the vapor barrier at the location where the chimney or other component pene-

trates the exterior of the structure.

NOTE:
Top sections of chimney must be removable to allow maximum clearance of 13.5 ft. (411cm) from
ground level for transportation purposes.

Burn wood only. Other types of fuels may generate poisonous gases (e.g. carbon monoxide)

Mobile Home Combustion Air adaptor

can be routed out the back wall or

through the floor.

Whether flat roof or sloped, the chim-
ney must penetrate the roof by
36” (.91m) on the high side and be at
least 24” (.61) higher than anything
within 10’ (3m)

Use only listed

double wall con-

nector for mobile

home installs

Listed UL 103 HT
or ULC S629
chimney