When a grounding strip is unavailable, Own in, Figure – H3C Technologies H3C WX5000 Series Access Controllers User Manual

Page 30

Advertising
background image

3-10

Figure 3-16

Ground the access controller through a grounding strip

(1) AC power socket

(2) Grounding terminal

(3) PGND wire

(4) Grounding strip

The fire main and lightning rod of a building are not good grounding options. The ground wire of the
access controller should be connected to the grounding system in the equipment room.

When a grounding strip is unavailable

1) If earth is available nearby and allows a grounding body to be buried

Hammer an angle steel or steel pipe longer than 0.5 m (1.64 ft) into the earth. In this case, weld the
yellow-green PGND wire of the access controller onto the angle steel or steel pipe, and treat the joint for
corrosion protection.

Figure 3-17

Ground the access controller through a grounding body

(1)

(2)

(3)

(4)

(5)

(1) AC power socket

(2) Grounding terminal

(3) PGND wire

(4) Earth

(5) Angle steel

2) If no grounding body is allowed to be buried