MAESTRO — Installation and Service Manual

299

Software Upgrade Procedure

3.

Right-click on the FPGA version number in the “Running>>” row and
in the FPGA column, of the selected Processor. A window similar to the
one seen in

Figure 189

appears.

Figure 189. Processor Board Boot ROM and FPGA/CPLD Update Window

4.

Verify that the date that appears in the “Loaded” column for the boot
ROM is Dec. 14 2006.

Note

If you see an older date or no date at all, the Boot ROM should be updated
(See the example in

Figure 189

). Stop the Installation process and then

contact Grass Valley Technical Support for update instructions.

5.

Repeat

Step 1

above and following steps if there is another Processor

(channel) in the system. If not, go to

Step 6

.

6.

In the Maestro Deployment Control Center window, select the control
panel for which you wish to check the Boot ROM version.

For a hardware control panel, this will be a CP Panel Server board.
For a GUI control panel, this will be a PCI Panel Server board.

7.

Right-click the FPGA version number in the “Running>>” row of the
selected Control Panel. A window similar to the one seen in

Figure 190

appears.