33 frequency reference loss detection, Frequency reference loss detection -57 – Yaskawa V7 Drives User Manual

Page 109

Advertising
background image

5-57

n

n 0

0 6

6 4

4 :: Frequency Reference Loss Detection

Factory setting: 0

0 (disabled)

Range: 0 or 1

The reference loss detection function is either enabled or disabled, based on the setting of n

n 0

0 6

6 4

4.

When enabled (data " 1 "), the reference loss detection compares the change in reference with
respect to time. If the reference decreases by 90% in more than 0.4 seconds, the drive will
decelerate to the set reference; if the reference decreases by 90% in less than 0.4 seconds, the
drive will continue to operate at 80% of the output frequency. To regain control of output
frequency, either exceed the set reference (80% of reference) or initiate a STOP command. If Auto
Reference is less than Fmax (n

n 0

0 1

1 1

1) x .05, this function is not performed.

FWD RUN

COMMAND

AUTO

REFERENCE

GPD 515

OUTPUT

FREQUENCY

80%
REF

10%

80%
FREQ.

0.4 SEC

0.4 SEC

T

Tiim

miin

ng

g C

Ch

ha

arrtt

5

5..3

33

3 F

FR

RE

EQ

QU

UE

EN

NC

CY

Y R

RE

EF

FE

ER

RE

EN

NC

CE

E L

LO

OS

SS

S D

DE

ET

TE

EC

CT

TIIO

ON

N

Note: This function applies to frequency references at terminal FR, RP or 2CN (Multi-Function Analog Input).

Undertorque detection is used to compare Drive output current/torque with the undertorque detection level.
When the output current is equal to or less than the defined level, an undertorque condition exists. This will be
indicated as a

UL3 fault on the Digital Operator. This feature can be selected to operate over a wide range of

conditions.

A.

n117 : Undertorque Detection

Factory setting:

0

This constant determines whether the undertorque detection function of the Drive is enabled, under what
conditions it will detect for undertorque, and what operation it will perform after detecting an undertorque.

Operation

Undertorque

After

Detection

Setting

Disabled

Detection

Condition

0

Disabled

——

——

1

Undertorque

Continues

Only at set frequency

2

Undertorque

Coast to stop

Only at set frequency

3

Undertorque

Continues

At all times except during
stopping or DC injection braking

4

Undertorque

Coast to stop

At all times except during
stopping or DC injection braking

5.34 UNDERTORQUE DETECTION