N050, N056, Table 5-2 – Yaskawa V7 Drives User Manual

Page 75: Thru, Data settings

Advertising
background image

5-23

Continued

5.18 MULTI-FUNCTION INPUT TERMINALS (Term. S1-S7)

DATA

FUNCTION

DESCRIPTION*

FWD/REV selection (for

MUST BE SET ONLY IN

n052 . Redefines terminals:

0

3-wire control)

S1 = Run; S2 = Stop;
S3 = FWD/REV select

1

Forward Run/Stop command

Closed = Run Forward (2-wire control)

(for 2-wire control)

Open = Stop

2

Reverse Run/Stop command

Closed = Run Reverse (2-wire control)

(for 2-wire control)

Open = Stop

Drive trips; Digital Operator displays "

EFX ",

3

External fault (N.O. contact input)

where X is 1-7, corresponding to the terminal,

4

External fault (N.C. contact input)

S2-S6, which is receiving the fault input signal

5

Fault Reset

Resets fault, only if RUN command is not present

6

Multi-step frequency ref. select A

7

Multi-step frequency ref. select B

See paragraph 5.11B

8

Multi-step frequency ref. select C

9

Multi-step frequency ref. select D

10

Jog selection

Closed = Jog selected See paragraph 5.12

11

Accel/decel time selection 1

Open = Accel/decel by

n019 / n020

Closed = Accel/decel by

n021 /n022

See paragraph 5.2

12

External base block

Closed = Shuts off the Drive output

(N.O. contact input)

(frequency command is held)

13

External base block

See paragraphs 5.18B, 5.18C

(N.C. contact input)

14

Speed Search 1

Closed * = Speed Search operation from

maximum frequency

See paragraph 5.18D

15

Speed Search 2

Closed * = Speed Search operation from set frequency
See paragraph 5.18D

16

Accel/Decel Hold

See paragraph 5.18F

17

Remote/Local selection

See paragraph 5.18A

Drive operation & reference/

Open = Operates according to setting of

n003 & n004

18

serial communication selection

Closed = Operates from serial communication
See paragraph 5.13

Fast Stop - Fault

Open = No effect

19

(Normally Open Contact)

Closed = If

n005 = 0, ramp to stop using n022

Closed =

If

n005 = 1, coast to stop

Fast Stop - Alarm

Open = No effect

20

(Normally Open Contact)

Closed = If

n005 = 0, ramp to stop using n022

Closed =

If

n005 = 1, coast to stop

Fast Stop - Fault

Open = If

n005 = 0, ramp to stop using n022

21

(Normally Closed Contact)

Open =

If

n005 = 1, coast to stop

Closed = No effect

Fast Stop - Alarm

Open = If

n005 = 0, ramp to stop using n022

22

(Normally Closed Contact)

Open =

If

n005 = 1, coast to stop

Closed = No effect

26

Overheat Pre-Alarm OH3

Open = No effect
Closed = OH3 alarm

27

Accel/Decel Time Select 2

See paragraph 5.2

34

Up/Down function

See paragraph 5.18E (can only be set in

n056)

35

Loop Test (Serial Communications)

See paragraph 5.14D
Can only be set in

n056

Table 5-2.

n050

thru

n056

Data Settings

* All contact closures must be maintained, except for speed search, which may

be momentary (see paragraph 5.18D).