2-3

DIGITAL OPERATOR

DESCRIPTION

KEY SEQUENCE

DISPLAY

Table 2-1. Open Loop Vector Startup Procedure - Continued

Set motor rated current.
(This can be obtained from
the nameplate of the motor.)

Press and hold

until n036 is dis-

played on the digital operator.

Then press

.

Use the

&

keys until the

number in the display matches the motor
rated current.

Then press

.

DATA
ENTER

V

V

DATA
ENTER

V

Set the motor rated slip.
This can be calculated by
using the following formula:

Slip = (Ns-Nr) * P

120

Where:
Ns = Motor synch. speed

(2)

Nr = Motor rated speed
P = Number of motor poles

Example:
Slip = (1800 - 1725) * 4

120

Slip = 2.5

Press and hold

until n106 is dis-

played on the digital operator.

Then press

.

Use the

&

keys until the

number in the display matches the calculated
slip value (see equation at left).

Then press

.

DATA
ENTER

V

V

DATA
ENTER

V

Prepare to test run the
drive from the Digital
Operator.
Motor should be
disconnected from the load.

This will set the drive into the
“Local” mode and bring up
the motor current display.

Press and hold

several times until

the

LED is lit.

Press the

key once.

Display the drive’s output current by pressing

four times. Turn the Digital Operator

Pot all the way to the left (counter-clockwise.

DSPL

V

LO/RE

DSPL

PRGM

PRGM

PRGM

PRGM

LO/RE

LO/RE

IOUT

(1)

(1)