n067 : Analog Monitor Gain

Factory Setting:

1.00

Range: 0.01 to 2.00

This constant is used to calibrate the meter connected to terminals AM & AC.

n150 : Pulse Monitor Output

Factory Setting:

0

Frequency Output/Reference

Range: 0, 1, 6, 12, 24, 36, 40 - 45

At the factory setting of “0” a pulse train frequency of 1440 Hz will be output when output frequency
is 100% .

When connecting peripheral devices the following load limitations must be considered.
When using output as a sourcing output:

When used as a sinking input:

Pulse monitor output

1440 Hz

Output frequency

100 %

Pulse

AM

AC

Max output voltage (V)

Load Impedence (K ohms)

+5V

1.5K ohms to 3.499K ohms

+8V

3.5K ohms to 9.99K ohms

+10V

10K ohms or more

Continued

5.17 MULTI-FUNCTION ANALOG MONITOR OUTPUT (Term. AM & AC)

SETTING

DESCRIPTION

0

1140Hz/ Max. frequency (n011)

1

1F: Output frequency x 1

6

6F: Output frequency x 6

12

12F: Output frequency x 12

24

24F: Output frequency x 24

36

36F: Output frequency x 36

40

1140Hz/Max. frequency (n011)

41

1F: Frequency reference x 1

42

6F: Frequency reference x 6

43

12F: Frequency reference x 12

44

24F: Frequency reference x 24

45

36F: Frequency reference x 36

External power supply (v)

+12VDC +/-5%

Sinking current (mA)

16mA or less

n067 = 0.30

100%

MAX. OUTPUT
FREQUENCY

Factory Setting

OR CURRENT.

(

n067 = 1.00)

0

3 V

10 V

ANALOG OUTPUT

5-21