5-20

n065 : Monitor output Selection

Factory Setting:

0

Range: 0 – 1

Analog output AM & AC can be used as a pulse train output (output frequency monitor only).

n066 : Multi-function Analog Output

Factory Setting:

1.00

Range: 0 – 5

The monitor output provides a 0-10 Vdc signal
proportional to either output frequency or output current
between terminals AM & AC:

0 = 0-10 Vdc proportional to output frequency

(10V = 100% of maximum frequency)

1 = 0-10 Vdc proportional to output current

(10V = 100% of drive rated current)

2 = 0-10 Vdc proportional to DC Bus Voltage

(10V = 400 Vdc [800 Vdc])

3 = 0-10 Vdc proportional to motor torque

(10V = motor rated torque)

4 = 0-10 Vdc proportional to output power

(10V = drive capacity (KW))

5 = 0-10 Vdc proportional to output voltage

(10V =

n012 (Voltage max))

6 = 0-10 Vdc proportional to frequency reference

Drive

AM

Analog

output

AC

(0-10 Vdc)

MULTI-
FUNCTION
MONITOR
OUTPUT

+ –

FREQUENCY / CURRENT

METER

(1mA FULL SCALE)

5.17 MULTI-FUNCTION ANALOG MONITOR OUTPUT (Term. AM & AC)

SETTING

DESCRIPTION

0

Analog monitor output

1

Pulse train output (output frequency monitor)

n010 : Operator Connection Fault Detection

Factory setting:

0

Selection

Range: 0 or 1

Set this parameter to “1” only if the drive should shut down immediately if the Digital Operator is dis-
connected while the drive is running. When set to “0”, the fault will not occur until after the drive has
been stopped.

n081 : Momentary Power Loss Ride-thru

0

= Disabled (Factory setting)

Protection

1

= Enabled – 2 sec. power loss

ride-thru

2

= Enabled – indefinite power loss

ride-thru, provided control
power is maintained

The setting of this parameter either enables or disables the ride-thru feature of the Drive. If
disabled, the unit will stop immediately whenever a power loss occurs. If enabled, the Drive will
continue to operate during a momentary power loss of up to 80%, but if the loss exceeds the
identified time period, the Drive will stop.

5.16 MOMENTARY POWER LOSS RIDE-THRU

5.15 MISCELLANEOUS PROTECTIVE FUNCTIONS