Example 3: Remote Sequence (3-Wire) & Local Reference (Digital

Operator)

This configuration is best when a person rather than an external controller (PLC, relay, etc.) controls the drive.

OPERATION:

• The frequency reference comes from the digital operator pot.

• Close pushbutton (PB1) momentarily while pushbutton (PB2) is closed, and the drive will run at the

frequency setting in U1-01. Pushbutton (PB1) does

NOT need to be maintained.

• Open pushbutton (PB2) at any time and the drive will stop.

• If switch (SW1) is open, the drive will run in the forward direction. If switch (SW1) is closed, the drive will

run in the reverse direction. Switch (SW1) can be operated with the drive running at any speed.

• If the drive is put in the “Local” mode using the LO/RE quick start LED, the drive will behave the same as

illustrated in Example 1.

Table 4: Programming Required For Remote 3-wire Sequence & Local Reference

FS

FR

FC

DATA
ENTER

DSPL

RUN

MIN

MAX

STOP

FOR/REV

START

Start

Stop

Forward

(SW1)

(PB2)

(PB1)

Reverse

S1

S2

S3

S4

S5

S6

S7

SC

STOP

RESET

FREF

FOUT

IOUT

MNTR

PRGM

LO/RE

F/R

Shield (Drain Wire)

To Terminal

Control Wiring Schematic

0. 0 0

Parameter

Display

Description

n001

11

n001

4

n004

0

n036

Set Motor FLA

The drive will perform a 3-wire reset.

Setting this value will reset all parameters to their original factory
settings (all previous adjustments will be lost).

When the drive

completes the reset, this parameter returns to a value of 1.

CAUTION

After doing the reset above, the password parameter returned to a
1. Change it to a 4 to get access to all parameters in the drive.
This parameter sets the reference (motor speed) to come from the
digital operator potentiometer (local).
Enter the motor’s full load amps (as shown on the motor
nameplate).