34 : Up/Down Function

Programming data " 34 " for

n056 (multi-function input terminal) allows the S6 / S7 inputs to be

used for Up/Down frequency setting.

NOTES:

1. Parameter

n055 will not be valid when n056 is set to " 34 ".

2. Jog has priority over Up/Down.

3. Up/Down has priority over Multi-step Frequency inputs.

4. Upper limit speed is set by the formula:

n011 (Fmax) x

n033 (Freq. Ref. Upper Limit)

100

5. Lower limit speed is from

n034 , Frequency Reference Lower Limit.

6. See section 5.10 for information on the Up/Down hold memory.

EXAMPLE:

n056 Data 34: Up/Down function

Drive

S6

DOWN

S7

UP

SC

0V

DOWN

o o

UP

o o

INPUT SIGNAL

Term. S6 Term. S7

FUNCTION

DOWN UP
Open

Open

HOLD

Open

Closed

DOWN (Frequency command approaches minimum
output frequency or frequency command lower limit,
whichever is larger)

Closed Open

UP (Frequency command approaches frequency
command upper limit)

Closed Closed

HOLD

5.18 MULTI-FUNCTION INPUT TERMINALS (Term. S1-S7)