KACO blueplanet 6400xi User Manual

Page 11

Advertising
background image

Page 12

blueplanet Operating and Installation Instructions 6400xi - 7600xi

S e c t i o n 4 ·

O p e r a t i o n

Status

Display

Explanation

10

Temperature too high inside

The temperature in the unit has become too high (> 176 °F). When the
internal reaches 158 °F, the inverter limits the power. An internal tem-
perature of 176 °F is only reached if convection cooling is impeded by
external factors, e.g. by covering the cooling fi ns.

18

Error current switch-off

An error current was detected by the RCD module. Notify your authorized
electrican.

19

Error isolation Generator

The insolation resistance of the PV+/PV- to ground is too low. Notify your
authorized electrican,

30

Error Measurement

The current and voltage measurements in the inverter are not plausible.
This can be caused by very dynamic weather conditions if there are quick
changes between low grid-feed power (e.g. 200 W) and high grid-feed
power (e.g. the maximum grid-feed power).

31

Error RCD module

An error was detected on the RCD module.

32

Error Selftest

The internal grid separation relay test has failed. If this internal error occurs
several times, notify your authorized electrician.

33

Error DC-gridfeeding

The DC feed into the grid has exceeded the permitted limit value. This grid-
feed can be impressed from the grid on the blueplanet inverter so that no
inverter fault exists. If this error occurs several times, notify your authorized
electrician.

34

Error Communication

A communication error has occurred in the internal data transmission. If this
error occurs several times, notify the service department.

35

Protection
shutdown

Protection shutdown of the software (AC overvoltage, AC overcurrent, DC
link overvoltage). This is not an error, but instead a grid-related shutdown.

36

Protection
shutdown HW

Protection shutdown of the hardware (AC overvoltage, AC overcurrent, DC
link overvoltage). This is not an error, but instead a grid-related shutdown.

38

Failure
PV-Overvoltage

The voltage of the PV generator is too high. The solar generator is wrongly
dimensioned. Notify your authorized electrician.

41

Line failure
Undervoltage

The voltage of the grid-feed phase is too low. The grid cannot be fed
into. This error can be grid-related.

42

Line failure
Overvoltage

The voltage of the grid-feed phase is too high. The grid cannot be fed
into. This error can be grid-related.

48

Line failure
Underfrequency

The line frequency is too low. This error can be grid-related.

49

Line failure
Overfrequency

The line frequency is too high. This error can be grid-related.

51

Line failure overvoltage L1

Phase voltage L1 is above the set maximum phase voltage.

52

Line failure undervoltage L1

Phase voltage L1 is below the set maximum phase voltage.

53

Line failure overvoltage L2

Phase voltage L2 is above the set maximum phase voltage.

54

Line failure undervoltage L2

Phase voltage L2 is below the set maximum phase voltage.

55

Error DC link

The voltage at the DC link is too high, or the DC link cannot be charged
(IGBT damage).

57

Waiting for reactivation

Waiting for reactivation after an error.

58

Overtemperature
controlling unit

The temperature is too high. To avoid damage, the grid-feed was stopped.
Provide for suffi cient ventilation.

59

Error self test

An error occurred during the buffer inspection.

Internal error EPROM

An error occurred in the EPROM.

No parameters

Error, no parameters.

Table 4.2:

Fault signals