Inverter – Electrical data

Model

6400xi

7600xi

Max. degree of effi ciency

97.2 % @ 240 V

AC

96.9 % @ 208 V

AC

97.1 % @ 240 V

AC

97.0 % @ 208 V

AC

CEC degree of effi ciency

96.5 % @ 240 V

AC

96.5 % @ 208 V

AC

96.5 % @ 240 V

AC

96 5 % @ 208 V

AC

Internal consumption

Night shutdown: 0.4 W @ 240 V

AC

/ 0.3 W @ 208 V

AC

Operation: < 5 W

Minimum grid-feed power

35 W

Maximum Output Fault Current (AC) and
Duration

120 A / 100 μs

Maximum Input Short Circuit Current

36 A

Maximum Input Source Backfeed Current
to Input Source

0 A

Synchronization In-Rush Current

0 A

Surge protection

tested to 6 kV

Voltage and Frequency Trip Time

< 160 ms

Voltage Trip Limit Accuracy

1.5 % of nominal value

Frequency Trip Limit Accuracy

± 0.06 Hz

Trip Time Accuracy

± 0.1 %

Circuit design

self-commutated inverter

Clock frequency

17 kHz / 9 kHz

Grid monitoring

complies with IEEE 1547