S e c t i o n 7 ·

M a i n t e n a n c e

7 Maintenance

!

DANGER

Risk of fatal injury by electric shock at live

connections. Lethal voltages are still present in
the inverter and the connection box even after the
electrical connections have been disconnected.

Wait fi ve minutes before reaching into the

inverter and the connection box.

When working on the photovoltaic modules, the

current must be switched off on the inverter and
the solar installation with the aid of the DC dis-
connect switch on the connection box and the
external AC disconnect switch.

ACTION

Switch off the line voltage and the solar generator with the
aid of the DC disconnector (I = on or energized / O = off or
deenergized) and the external AC switch.

7.1 Cleaning the fan

If the fan is only covered with loose dust, it can be cleaned with
the help of a vacuum cleaner or a soft brush.

If the fan is very dirty, or if it s defective, it can be removed.

7.2 Removing the fan

If the fan is very dirty or defective, proceed as follows:

!

DANGER

Danger due to lethal voltages.

1.

Switch the DC disconnect and the external AC discon

nect to the OFF (0) position to de-energize the inverter

and lock out to prevent inadvertent energizing of the

inverter during service.

2.

Wait 5 minutes for the internal components of the

inverter to discharge.

3.

Remove the two inverter hinged door screws and open

door.

4.

Disconnect the fan connections, labeled with „Lüfter“.