Table 2-6, ac grounding electrode conductor sizing – Magnum Energy Mini Magnum Panel (MMP Series) User Manual

Page 43

Advertising
background image

©

2013 Magnum Energy, Inc.

Page 34

Installation

2.10.1 Sizing the Grounding Electrode Conductors

AC Side – The size of the AC Grounding Electrode Conductor (GEC–AC) depends on the size of

the largest ungrounded conductor feeding the AC load center. One #8 AWG (8.4 mm

2

) copper

conductor will serve as an AC Grounding Electrode Conductor (GEC–AC) for AC power conductors

smaller than and including #2 AWG (33.6 mm

2

) copper. See

Table 2-6 for additional values.

Table 2-6, AC Grounding Electrode Conductor Sizing

Size of Largest Ungrounded

Conductor

Minimum Size of Grounding

Electrode Conductor

#2 AWG or smaller

#8 AWG

(8.4 mm

2

)

#1 to #1/0 AWG

#6 AWG

(13.3 mm

2

)

#2/0 or #3/0 AWG

#4 AWG

(21.1 mm

2

)

Over #3/0 AWG

through 350 kcmil

#2 AWG

(33.6 mm

2

)

DC Side – To size the DC grounding electrode conductor, you must fi rst determine which one of the

following three methods will be used to connect the DC and AC grounding points in the inverter’s

two electrical systems to the common “earth” ground.

Info: There are many variables to consider when choosing the size of the DC grounding

electrode conductor. The MMP enclosure provides the means to ground both the AC and

DC to a single ground, and when feasible, the Single Connection to Ground (Method

1) is recommended. In this method, the NEC allows a #6 AWG wire which makes the

overall installation simpler and less costly.

1.

Single Connection to Ground (Method 1): The AC Grounding Electrode Conductor

(GEC–AC) is bonded to the DC ground point and the DC Grounding Electrode Conductor (GEC–DC)

is the only connection to the grounding electrode, which must be a rod, pipe, or plate electrode

(see Figure 2-17).
Normally the size of the DC Grounding Electrode Conductor (GEC–DC) must be no less than the size

of the Battery Bank Negative Cable. However, in this method, since there is only one connection

to the ground rod, the NEC allows an exception that the DC grounding electrode conductor is

not required to be larger than #6 AWG (13 mm

2

) copper. The reasoning for allowing this smaller

grounding electrode conductor is that it is only required to stabilize the system voltage with respect

to earth, and the other properly sized conductors in each electrical system will safely carry any

fault currents if they occur.

DC

S

OURCE

M

AIN

AC P

ANEL

H

OT

1

N

EUT

G

ND

H

OT

2

MMP

AC

S

OURCE

DC side dedicated

DC Electrical

System

AC Electrical

System

Grounding System

G

ND

P

OS

N

EG

GBB

SBJ

GEC-DC

GE

GBB

SBJ

M

AGNUM

I

NVERTER

GEC-AC

GC-DC

BAT

GC-AC

HOT 1

HOT 2

NEUT

BAT

E

NCLOSURE

Figure 2-17, Single Connection to DC Ground Rod (Method 1)

Advertising