Magnum Energy Mini Magnum Panel (MMP Series) User Manual

Page 45

Advertising
background image

©

2013 Magnum Energy, Inc.

Page 36

Installation

2.10.2 Equipment Grounding Conductor

The MMP enclosure and all other noncurrent-carrying exposed metal surfaces in the entire electrical

system that may be accidentally energized must be grounded. The equipment-grounding conductor

must be sized to safely carry the maximum ground-fault current likely to be imposed on it from

where a ground-fault may occur.
AC Side – When the AC circuit breaker provided in the MMP enclosure is being used as the

inverter’s AC overcurrent protection device, the AC Equipment Grounding Conductor (EGC–AC)

for the inverter is based on the AC breaker size provided (#10 AWG for all MMP models). Connect

the AC equipment-grounding conductor from the inverter’s AC ground connection to the Ground

Busbar (GBB) in the MMP enclosure (Item 8 in Figure 1-2 or 1-4).
DC Side – When the DC circuit breaker provided in the MMP enclosure is being used as the

inverter’s DC overcurrent protection device, the DC Equipment Grounding Conductor (EGC–DC) for

the inverter is based on the DC breaker size provided (#6 AWG for MMP175 models, #4 AWG for

MMP250 models). Connect the DC equipment-grounding conductor from the inverter’s DC ground

connection to the Ground Busbar (GBB) in the MMP enclosure (Item 20 in Figure 1-2 or 1-4).
If you are using AC or DC overcurrent protection that is different than that provided in the MMP

enclosure, or installing optional DC breakers inside the MMP enclosure, in accordance with the

NEC/CEC you must determine your equipment-grounding conductors based on the ampere rating

of the overcurrent device protecting the circuit conductors. Use Table 2-7 to help determine the

equipment-grounding conductor. If the circuit conductors are oversized to compensate for voltage

drop, the equipment-grounding conductor must also be oversized proportionally.

Table 2-7, Equipment Grounding Conductor Sizing

Rating of Overcurrent

Device

Minimum Size of Copper

Ground Wire

15 amp

#14 AWG

20 amp

#12 AWG

30-60 amp

#10 AWG

100 amp

#8 AWG

200 amp

#6 AWG

300 amp

#4 AWG

400 amp

#3 AWG

2.10.3 System Bonding Jumper

The MMP enclosure provides the

single

point of ground [System Bonding Jumper (SBJ)] for the

AC and DC system. If the MMP enclosure is the central connection point for all ground wiring

(usually in an off-grid system) and there is no other connection from AC neutral or DC negative

to ground in the AC or DC system, then leave the ground bond connections in place. Remove any

other neutral-ground connection in the AC system, such as in other electrical sub-panels; or, any

negative-ground connection in the DC system.
For utility connected systems where the neutral and ground are already bonded in the main utility

circuit breaker box (AC distribution panel), the GREEN GROUND/NEUTRAL bonding wire MUST BE

REMOVED from the MMP enclosure. See Section 2.11 to remove this neutral-ground connection.

Info: Inverters and portable generators that have electrical outlets usually have the

neutral and ground bonded internally. These types of devices are not recommended to

be connected to the MMP/inverter system as they would fi rst need to be modifi ed to

separate the neutral and ground bonding internally.

For systems or devices that connect the DC negative to ground independently (i.e., separate

DC main electrical distribution panel or PV-GFP device), the Negative to Ground busbar (Item 1,

Figure 1-2 or 1-4) MUST BE REMOVED inside the MMP enclosure. See Section 2.12 to remove this

negative-ground connection.

Advertising