11 removing the ac neutral to ground connection, 12 removing the dc negative to ground busbar – Magnum Energy Mini Magnum Panel (MMP Series) User Manual

Page 46

Advertising
background image

Page 37

©

2013 Magnum Energy, Inc.

Installation

Steps to remove the DC negative-to-ground

connection:
1. Inside the MMP enclosure, locate the Nega-

tive to Ground Busbar (Item 1, in Figure 1-2

and 1-4). This busbar connects negative and

ground inside the MMP enclosure.

2. Remove the 5/16” fl ange nut (1/2” wrench)

holding the busbar to the DC Ground Stud

(Item 13, in Figure 1-2 or 1-4), and then re-

move the 3/8” brass bolt and washer (9/16”

wrench) from the bottom terminal of the DC

shunt (Item 12, in Figure 1-2 or 1-4).

3. After the Negative to Ground Busbar is re-

moved; reattach the fl ange nut on the DC

Ground Stud and the brass bolt/washer back

onto the DC shunt. Ensure the hardware

on the bottom terminal of the DC shunt is

stacked correctly. Note: Refer to Figure 2-9

to correctly stack the DC shunt hardware.

Steps to remove the neutral to ground connection:
1. Inside the MMP enclosure, locate the green

wire with the NEUTRAL-GROUND CONNEC-

TION label (Item 7, in Figure 1-2 or 1-4). This

green wire connects the neutral and ground

inside the MMP enclosure.

2. Loosen the screw and remove this green wire

from the Ground Busbar (Item 8, in Figure

1-2 or 1-4). Note: After this wire is removed,

remember to tighten the loose screw back

into the busbar to prevent it from being lost.

3. With this green wire removed, wrap electrical

tape around the bare end to insulate the wire

and prevent it from making contact with any

metal. Secure the green wire out of the way.

2.12 Removing the DC Negative to Ground Busbar

The MMP enclosure provides the single point of ground for the DC system by connecting the DC

shunt (battery negative connection point) to the DC Ground Stud using the DC Negative to Ground

Busbar (Item 1, in Figure 1-2 and 1-4). If the single negative-ground connection is made elsewhere

in the DC system—either at the battery terminal, inside a charge controller, or if you are installing

a PV-Ground Fault Protection (PV-GFP) device—this busbar must be removed to prevent multiple

negative-ground bonds. See Figure 2-21 to help remove the Negative to Ground Busbar.

Figure 2-21, Removing the DC

Negative to Ground Busbar

2.11 Removing the AC Neutral to Ground Connection

In installations where the MMP enclosure is powered from utility power or large permanently

installed generator systems, the AC neutral to ground connection is normally provided inside the

main AC electrical distribution panel. In these systems, the factory installed neutral to ground

connection in the MMP enclosure must be removed to prevent multiple neutral to ground bonds.

See Figure 2-20 to help remove the neutral to ground connection from the AC Ground Busbar.

Figure 2-20, Removing the AC Neutral

to Ground Connection

Neutral to

Ground

Connection

(Green Wire)

Ground

Busbar

Negative to Ground

Busbar

Bottom Terminal

(DC Shunt) Ground

Busbar

DC Ground

Stud

Advertising