2.15 Functional Test

After all electrical connections from the MMP enclosure to

the inverter, batteries, AC source, and

sub-panel

have been completed, follow these steps (refer also to Figure 2-26) to test the installation

of the MMP enclosure and to verify proper operation of the BYPASS switch breakers.

WARNING: During this functional test, the front cover is removed and exposes

personnel to potential dangerous voltages and shock hazards inside the MMP enclosure

that may cause damage, injury, or death. If you do not have experience working with AC

and DC voltage circuits, do not attempt this test—use an experienced electrical installer.

CAUTION: During this functional test, if any step cannot be verifi ed or is incorrect,

stop and recheck/correct the connections before proceeding to the next step.

1. Turn OFF all AC breakers (i.e., INV BYP, INV IN, and INV OUT) in the MMP enclosure.

CAUTION: Use a multimeter to verify the correct DC voltage for your particular inverter

model (i.e., 24-volt battery bank for a 24-volt inverter) and to ensure the polarity of

the battery voltage is correct [battery positive (+) connected to the inverter positive

terminal thru the DC circuit breaker and battery negative (–) connected to inverter

negative terminal thru the DC shunt].

CAUTION: Prior to turning on the inverter, turn OFF all inverter loads in the inverter

load panel (i.e., sub-panel).

2. After verifying that the battery bank voltage is proper for your inverter and that the battery

cable connections are the correct polarity, apply battery power to the inverter by turning the

DC disconnect breaker to the ON (up) position.

3. Turn the inverter ON.

a. Connect an AC voltmeter to the Inverter Output Terminals and verify the correct AC

output voltage of the inverter (depends on your inverter AC output voltage).

Info: If the inverter does not turn on—verify the DC connections to/from the inverter

to the battery, and/or refer to the Troubleshooting section for your particular inverter.

Info: If the inverter has a Search mode feature, the inverter’s AC full output voltage

will not be present/correct until Search is turned OFF, or by connecting a large enough

light bulb to bring the inverter out of Search. DO NOT connect anything but a light bulb

until all wiring and voltages are confi rmed to be correct.
If using a Magnum inverter, use a light bulb greater than 5 watts (5 watts is the default

setting) to bring the inverter out of Search mode; or, the Search mode can be turned

OFF with a remote control (ME-RC or ME-ARC).

4. Turn ON the INV OUT

1

breaker(s) in the MMP enclosure.

a. Ensure the inverter AC output voltage is passing thru the INV OUT (Inverter Output) breaker

by verifying the correct output voltage is present on the AC Output Terminals.

5. Turn ON the INV BYP

2

breaker(s) in the MMP enclosure.

a. Ensure the inverter AC output voltage is no longer present on the AC Output Terminals.

Note¹ – On MMPxxx-60S models, the INV OUT and INV IN breakers are physically ganged together

and turn ON and OFF as a single breaker.

Note

2

The INV BYP and INV OUT breakers are interlocked together. Physically turning ON will turn

OFF the other, and vice-versa.