3 connect power supply wiring, Connect power supply wiring, Caution – Emerson IFT9701 User Manual

Page 28

Advertising
background image

20

Model IFT9701 Transmitter Instruction Manual

Power Supply and Output Wiring

continued

4.3

Connect power supply wiring

Figure 4-1 shows the power supply wiring terminals.

Wiring terminals accommodate 20 AWG (0,5 mm²) to 16 AWG (1,5 mm²) wire. If the
transmitter has a DC power supply, see Table 4-1 for wire length and size guidelines.

Connect power supply wiring to the power supply terminals.

A switch may be installed in the power supply line. For compliance with low-voltage directive
73/23/EEC, a switch in close proximity to the transmitter is required.

Do not install power cable in the same conduit or cable tray as flowmeter cable or output
wiring.

The transmitter must be grounded with a maximum impedance of 1 ohm. Either the internal
ground screw or external case ground screw may be used as required by local policy or code.

Figure 4-1

Power supply wiring terminals

CAUTION

Incorrect voltage, or installation with power supply
on, could cause transmitter damage or failure.

Match power supply voltage with voltage indicated on
label in field wiring compartment.

Shut off power before installing transmitter.

– +

85-250 VAC

20-30 VDC

N L

If national standards are not in effect, adhere to these guidelines for grounding:
• Use copper wire, 14 AWG (2,5 mm²) or larger wire size.
• Keep all ground leads as short as possible, less than 1 ohm impedance.
• Connect ground leads directly to earth, or follow plant standards.
• For hazardous area installation in Europe, use standard EN 60079-14 as a guideline.

Field wiring
compartment

Sensor wiring
compartment

External ground screw

for power supply

Conduit opening for

power supply wiring

Internal ground screw

for power supply

Field wiring
compartment

Power
terminals

AC

transmitter

DC

transmitter

OR