To enter an internal damping value, use the menu below and follow these steps:

1. At the online menu, choose 4 (detailed setup).

2. At the detailed setup menu, choose 2 (configure field device variables).

3. At the configure field device variables menu, choose 1 (flow).

4. At the flow menu, choose 4 (flow damping).

5. Select the desired damping value.

6. Press F2 (send) to send the damping value to the flowmeter memory.

6.2.5

Flow direction

The configured flow direction (forward, reverse, or bi-directional) determines how flowmeter outputs
and totalizers will react when fluid flows through the meter. The flow direction arrow on the meter is
considered the "forward" flow direction, but the meter measures flow accurately in either direction.

To configure flow direction for the meter, use the menu below and follow these steps:

1. At the online menu, choose 4 (detailed setup).

2. At the detailed setup menu, choose 2 (configure field device variables).

3. At the configure field device variables menu, choose 1 (flow).

4. At the flow variables menu, choose 3 (flow direction), then choose the desired option. The

table below lists how outputs and totalizers are affected by the option that is chosen.

5. To send the flow direction to the flowmeter, press F2 (send).

1 Process variables
2 Diag/service
3 Basic setup
4 DETAILED SETUP
5 Review

1 Flo unit
2 Flo cutoff
3 Flo direction
4 FLOW DAMPING

1 Charize sensor
2 CONFIG FLD

DEV VAR

3 Config outputs
4 Device

1 FLOW
2 Density
3 Temp unit

1 Process variables
2 Diag/service
3 Basic setup
4 DETAILED SETUP
5 Review

1 Flo unit
2 Flo cutoff
3 FLO DIRECTION
4 Flow damping

1 Charize sensor
2 CONFIG FLD

DEV VAR

3 Config outputs
4 Device

1 FLOW
2 Density
3 Temp unit

Table 6-1

Effect of flow direction on outputs and totalizers

Fluid flow
direction

Output or
totalizer

Flowmeter configuration

Forward

Reverse

Fluid flowing
in same direction
as flow arrow
on sensor

Milliamp output

Output increases as flow rate
increases

Output goes to 3.8 mA

Pulse output

Output increases as flow rate
increases

Output remains at 0 Hz

Internal totalizers

Flow totals increase

Flow totals remain constant

Fluid flowing
in opposite direction
from flow arrow
on sensor

Milliamp output

Output goes to 3.8 mA

Output increases as flow rate
increases

Pulse output

Output remains at 0 Hz

Output increases as flow rate
increases

Internal totalizers

Flow totals remain constant

Flow totals increase