4.4

Connect output wiring

Figure 4-2 shows the milliamp and pulse output terminals.

Install twisted-pair, shielded cable, consisting of 20 AWG (0,5 mm²) to 16 AWG (1,5 mm²)
wire.

For basic information on milliamp output wiring, see Section 4.4.1.

For instructions on connecting the milliamp output to a Bell 202 multidrop network, see
Section 4.4.2.

For instructions on connecting a HART device to the milliamp output, see Section 4.4.3.

For instructions on pulse output wiring, see Section 4.4.4.

Figure 4-2

Output wiring terminals

Table 4-1

Wire guidelines for DC power supply

Wire size

Wire length

16 AWG (1,5 mm²)

1500 feet (450 meters)

18 AWG (0,75 mm²)

1000 feet (300 meters)

20 AWG (0,5 mm²)

600 feet (200 meters)

• Terminate output cable shielding at gland or conduit fitting.
• 360° termination of shielding is not necessary.
• Do not terminate shield inside wiring compartment.
• The pull-up resistor must be of sufficient value to limit the total loop current to less

than 500 ohms. Refer to Section 4.4.4 to determine the pull-up resistor needed.

Field wiring
compartment

Sensor wiring
compartment

Case ground

Active milliamp output

Internally powered

Passive pulse output
Requires pull-up resistor
to external 5–30 VDC
power supply

Conduit opening
for output wiring