Other methods – Retrotec DucTester 200 Series Residential Applications User Manual

Page 58

Advertising
background image

Page 58 of 91
©Retrotec Inc. 2015

the Open Range. Set the pressure to the just measured supply plenum pressure. Press

[Set Pressure]

and enter the previously measured supply plenum pressure. Read the CFM result directly from the
gauge after waiting for at least one minute to let the measurement settle down.

For example, if the pressure in the supply plenum is 70 Pa, press

[Set Pressure]

,

[70]

,

[Enter]

to get the

Blower Door to recreate the original pressure in the plenum. Read the CFM result directly from the
gauge

If “TOO LOW” or “----“appears the pressure in the plenum is too high to get an accurate reading. Repeat
the procedure but move the Static Pressure Probe to measure the pressure farther away from the air
handler.

9.9 Other methods

Temperature rise and other standard HVAC methods exist but are not covered here.

Advertising