For most ducts, the n value is usually 0.60. For the flow at 50 Pa, replace “25” with “50.”

Rather than using the equation in the situation where the 25 Pa test pressure cannot be achieved, you
can use tables with the factors already calculated and the following procedure.

Take a flow (CFM) reading at the pressure achieved and multiply by the "Cannot reach 25 Pa factor”
from Table 14 to get an estimate of the flow that would result at 25 Pa.

For example: if you read 600 CFM at a building pressure of 19 Pa, the "Cannot reach 25 factor" from
Table 14 is 1.18. To get the estimated flow at 25 Pa, make the following calculation:

600 CFM × 1.18 = 708 CFM

Thus the estimated result for CFM at 25 Pa will be 708 CFM.

The factors depend on the n value chosen. Table 14 is for n of 0.60 which is typical for ducts.

Table 14: Factors for when a duct pressure of 25 Pa cannot be reached (assumed n value of 0.6).

Pressure

achieved

Cannot reach

25 factor

25

1.00

24

1.02

23

1.05

22

1.08

21

1.11

20

1.14

19

1.18

18

1.22

17

1.26

16

1.31

15

1.36

14

1.42

13

1.48

12

1.55

11

1.64

10

1.73

9

1.85

8

1.98

7

2.15

6

2.35

5

2.63

Cannot Reach 50 Pa Factors

Rather than using the equation in the situation where the 50 Pa test pressure cannot be achieved, you
can use tables with the factors already calculated and the following procedure. Take a flow (CFM)
reading at the pressure achieved and multiply by the "Cannot reach 50 Pa factor” from Table 15 to get
an estimate of the flow that would result at 50 Pa.