4.4.1. Measurement procedure for "2P" test mode
1. Select "2P" earth measurement mode using the F1 key.
2. Connect the Black, Red, Green and Blue cables to the corresponding input terminals of the

instrument T1, T2, T3, T4 (see possible connections in the following picture).

3. Connect the black, and green cables to the earth plant and red and blue cables to the

auxiliary rod.

B2

B3

B4

B1

2 points earth resistance measurement


4. Press

the

START/STOP key. The instrument starts the test.

START

STOP


)

EARTH

0.96

2P

0.93

At the end of the test the instrument
displays the values alongside.

Average value of earth resistance calculated over
the number of test displayed.

Resistance value
measured

Mode “2P”.


WARNING

Never disconnect the test leads while the word “Measuring” is being
displayed.

SAVE

SAVING:

The tests can be stored pressing the SAVE key twice (refer
to paragraph 5.1).



Note: If START/STOP key was pressed and held, the instrument takes more

consecutive tests.


5. When a new value is acquired the instrument emits a short sound and calculates the

new average value.