D. install chimney air kit, E. install ceiling firestops – Heatiator Heatilator Wood Burning Fireplace SC60 User Manual

Page 27

Advertising
background image

27

Figure 8.4 Assembling Chimney Sections

ROOM ABOVE (non-insulated ceiling)

ATTIC ABOVE (insulated ceiling)

B

A

Ceilng firestop from

bottom

Ceiling firestop from

top

Note:

Use same dimensional lumber for framing

ceiling firestop and joists.

Figure 8.5 Installing the Ceiling Firestop

• Support the pipe during construction and check to be

sure inadvertent loading has not dislodged the chimney

section from the fireplace or at any chimney joint.

• Attach a straight chimney section or an offset to the top

of the fireplace.

• Place inner flue to the inside of the chimney section below

it. Place the outer casing outside the outer casing of the

chimney section below it. Refer to Figure 8.4.

NOTICE: Chimney sections cannot be disassembled

once locked together. Plan ahead!

• Lock chimney sections and/or offsets/returns together by

pushing downward until the top section meets the stop

bead on the lower section.

• Pull on the top section to make sure it is fully engaged

and will not separate.

• You may use #6 or #8 sheet metal screws no longer than

1/2 in. (13 mm) to fasten chimney sections together. Do

NOT penetrate inner flue.

WARNING! Risk of Fire! You MUST use screws (pro-

vided) to fasten offset/returns to chimney sections to

keep the chimney parts from twisting. Failure to do so

could cause fire.

• Fasten offset/returns to chimney sections. Insert the

screws (provided) through the predrilled holes. Do NOT

penetrate inner flue.

• Secure chimney returns with hanger straps provided;

fasten to studs or joists.

• Vertical straight runs of chimney must be supported every

35 ft (10.7 m).

C. Assemble Chimney Sections

WARNING! Risk of Fire! DO NOT install substitute or

damaged chimney components.
• Use only those components described in this manual.
Substitute or damaged chimney components could impair

safe operation and cause overheating and fire.

D. Install Chimney Air Kit

• Required in Canada.

• Follow instructions provided with this accessory.

• Install a ceiling firestop whenever chimney penetrates

ceiling/floor.

• Mark and cut an opening in ceiling as shown in

Figure 8.5.

• Frame the opening with the same size lumber used in

the ceiling joists.

• Nail the ceiling firestop to the bottom of the ceiling joists

when there is a room above.

• Use an attic insulation shield if the ceiling is insulated.

The ceiling firestop may then be attached above or below

the joists.

E. Install Ceiling Firestops

CAUTION! Risk of Fire! Ceiling firestops must be used

whenever the chimney penetrates a ceiling/floor.

• Chase construction requires ceiling firestops at each

floor or every 10 ft (3.05 m) of clear space.

• The ceiling firestop slows spread of fire and reduces cold

air infiltration.

WARNING! Risk of Fire! DO NOT seal area between

firestop opening and chimney pipe except where they

enter the attic or leave the warm air envelope of the

home (use 600° F sealant).

Heatilator • SC60 • 32838 • Rev AG • 7/12

Catalog #

A

B

Angle

in.

mm

in.

mm

FS338

14-1/2

368

14-1/2

368

FS339

14-1/2

368

18-3/8

467

15°

FS340

14-1/2

368

23

584

30°

Advertising