F. Sidewalls/Surrounds

• Adjacent combustible sidewalls must be located

a minimum of 12 in. (305 mm) from the fireplace

opening.

• Combustible or non-combustible mantel legs, surrounds

and stub walls may be constructed per Figure 11.12.

42 1/8 in.

[1070 mm]

36 in.

[914 mm]

12 in.

[305 mm]

14 1/2 in.

[368 mm]

12 in.

[305 mm]

10 3/4 in.

[273 mm]

FLUSH

FRONT

4 in.

[102 mm]

BRICK

FRONT

50° angle

39° angle

Figure 11.12 Mantel Leg or Wall Projections (acceptable on both sides of opening)

G. Firebrick Installation

• The bottom firebrick is preinstalled.

• Remove side brick pieces from inside of fireplace.

• Set bottom of side brick (three bricks per side) into lower brick support. See Figure 7.13.

• Lift up outer edge of upper brick support just enough to pivot brick under channel.

• Push upper brick support down over bricks to hold the bricks in place.

• Repeat procedure for other side.

Upper Brick

Support

Lower Brick

Support

Channel

Figure 11.13 Side Brick Installation

Center

Brick

Brick

Support

Bracket

Gas

Line

Figure 11.14 Gas Line Installation