Firebox

Repack

insulation

knockout

Combustible

materials

Maintain air clearance

to combustibles.

Gas line

Combustible materials

may be located at zero

clearance to gas line

beyond 4 in. (102 mm)

from fireplace side.

Gas line

1 1/2 in. (38 mm)

air space around

pipe

Refractory

Seal with

fireplace mortar

or non-combust-

ible sealant

4 in.

(102 mm)

Outer shell

of fireplace

Figure 12.1 Gas Line Installation

12

Accessories

A. Gas Log/Lighter Provision

WARNING! Fire and/or Asphyxiation Risk! Use with

solid wood fuel or decorative gas appliance only. Gas fire

generates fumes.

DO NOT install unvented gas logs

• Damper must be locked fully open when gas logs are

installed

A certified gas log lighter or decorative gas log set can be

installed in this fireplace.
• Maximum input is 100,000 BTU/hr.

• Decorative gas appliance must be certified to

ANSI

Z21.60 “Standard for Decorative Gas Appliances for

Installation in Vented Fireplaces”.

• Must be installed in accordance with the

National Fuel

Gas Code, ANSI Z223.1.

• A gas log set must incorporate a gas shutoff.

• Gas log set requires the damper to be locked fully

open.

• A listed automatic damper system with safety interlock

may be used in this fireplace with only compatible,

listed gas log sets. See damper system manufacturer’s

instructions.

• Knockouts are provided on both sides of the fireplace

and in refractories for 1/2 in. (13 mm) iron pipe.

• Seal refractory around pipe with fireplace mortar or a

non-combustible sealant.

B. Wood Burning Inserts

WARNING! Risk of Fire! Improper installation of wood in-

serts may cause fireplace or chimney system to overheat.

If a wood burning insert is being installed in this fireplace,

Hearth & Home Technologies recommends full reline of

the chimney.
• Cooling air openings at the top of the chimney must not

be obstructed in any manner.

• Hearth & Home Technologies recommends securing the

reline at the top of the flue and using the cap certified for

use with this fireplace system.

Heatilator • SC60 • 32838 • Rev AG • 7/12