B. sequence of operation and timing charts, Refrigerators – continuous operating mode – Hoshizaki HUR40A(-D) User Manual

Page 13

Advertising
background image

13

Note:

1) Cut-on, cut-off, and cabinet temperature are read by the same sensor, called the

"cabinet thermistor."

2) The defrost thermistor reads the evaporator temperature.
3) There is a five second evaporator fan startup delay when the compressor and

fan would otherwise start together.

B. Sequence of Operation and Timing Charts

For details on operating modes, see "II.D.4. Operating Modes."

1. Refrigerators – Continuous Operating Mode

a) Sequence of Operation

Five minutes after
defrost heater off
1. Compressor on
2. Condenser fan on

Five minutes after
compressor start-up
1. Evaporator fan(s) on
2. Frame heater(s) on
(Q6 and later)

One minute after evaporator
fan start-up "dF" no
longer displayed, cabinet
temperature displayed

Board Self Check
1. Frame heater(s) on
2. Evaporator fan(s) on

POWER ON

2-minute Delay
1. Compressor start-up
2. Condenser fan start-up

Cycle Off (Cut-out
temperature reached)
[Minimum 2 minutes]
1. Compressor off
2. Condenser fan off

Continue as
normal cycling

Cycle On (Cut-on
temperature reached)
[Minimum 2 minutes]
1. Compressor start-up
2. Condenser fan start-up

Defrost End
Defrost thermistor
reaches defrost
termination temperature,
or defrost timer reaches
1 hour
Defrost heater off

Defrost Start
Preprogrammed time interval
1. Compressor off
2. Evaporator fan(s) off
3. Frame heater(s) off (Q6 and later)
4. Condenser fan off
5. Defrost heater on
6. "dF" displayed