Alarm details and countermeasures, A. high temperature alarm (e1) – Hoshizaki HUR40A(-D) User Manual

Page 35

Advertising
background image

35

2. Alarm Details and Countermeasures

a. High Temperature Alarm (E1)

If the cabinet temperature exceeds the setpoint temperature by 14.4°F (8°C) or more for
more than x hours, "E1" is displayed. The default value of x is "2" (2 hours). The value
of x can be changed under F3 on the Settings and Diagnostics Menu. (0=No delay; 1=1;
2=2; 3=3 hours)

Note:

• After the machine has been turned off and then turned back on, the high

temperature alarm feature is not active until the cabinet temperature reaches the
lower setpoint temperature differential.

• The high temperature alarm feature operates even during defrost.

Reset Options
The alarm will automatically reset once the cabinet temperature reaches the lower setpoint
temperature differential.

Possible Causes
• The door is opened frequently or is not completely closed.
• Trouble with the compressor or a gas leak.
• Trouble with the cabinet thermistor (black).