4. Freezers – Energy Saving Operating Mode

a) Sequence of Operation

Note:

1) Cut-on, cut-off, and cabinet temperature are read by the same sensor, called the "cabinet

thermistor."

2) The defrost thermistor reads the evaporator temperature.

Five minutes after
defrost heater off
1. Compressor on
2. Condenser fan on

Five minutes after
compressor start-up
1. Evaporator fan(s) on

Eight minutes after evaporator
fan start-up "dF" no longer
displayed, cabinet temperature
displayed

Board Self Check
1. Frame heater(s) on
2. Evaporator fan(s)
cycles on and off

POWER ON

2-minute Delay
1. Compressor start-up
2. Condenser fan start-up
3. Evaporator fan(s) on
(continuously)

Cycle Off (Cut-out
temperature reached)
[Minimum 2 minutes]
1. Compressor off
2. Condenser fan off
3. Evaporator fan(s)
cycles on and off

Continue as
normal cycling

Cycle On (Cut-on
temperature reached)
[Minimum 2 minutes]
1. Compressor start-up
2. Condenser fan start-up
3. Evaporator fan(s) on

(continuously)

Defrost Start
Preprogrammed time interval
1. Compressor off
2. Evaporator fan(s) off
3. Condenser fan off
4. Defrost heater on
5. "dF" displayed

Defrost End
Defrost thermistor
reaches defrost
termination temperature,
or defrost timer reaches
1 hour
Defrost heater off