T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER

62-0255—07

16

Fig. 30. Setup - Sensors - Sensor A - 0-5V, 0-10V, OR

4-20MA - MIN and MAX Value (showing °F).

1.2.2.2.3. MIN or MAX VALUE

(Sensor A only;

0-5V, 0-10V or 4-20mA)
The minimum and maximum values display only for
Sensor A when its type is 0-5V, 0-10V or 4-20MA.

1. From the Sensor A selections, use the S and T

buttons to highlight MIN VAL or MAX VAL.

2. Press the X button to display the units.
3. Use the S and T buttons to increase/decrease the

desired value.

Sensor Ranges:

°F

-60.0 to 270.0

°C

-51.0 to 132.0

PSI

-500 to 500

IN WC

-30.0 to 30.0

%

0.0 to 100.0

PA

-3000 to 3000

KPA

-3000 to 3000

PPM

0 to 9990

NONE

-9999 to 9999

4. Press the X button to accept the units and return to

the Sensor A selections.

Fig. 31. Setup - Sensors - Sensor A - Calibrate.

1.2.2.3. CALIBRATE

(Sensor A or B)

Ensure that the wire size calibration value is within the
limits for the sensor.
• For temperature sensors, see “Temperature Sensor

Calibration” on page 10.

• For other sensors, see “Humidity, Pressure, and

Universal Sensor Calibration” on page 10.

1. From the Sensor A selections, use the S and T

buttons to highlight CALIBRATE.

2. Press the X button to display the calibration value.
3. Use the S and T buttons to increase/decrease the

desired calibration value.

Default: 0.0
Sensor Range Temperature: +/-10°F (+/-6°C)
Other Sensor Range: +/-10% of the Min to Max

values specified previously. See Table 3 on
page 10 for examples.

4. Press the X button to accept the value and return to

the Sensor A selections.

Fig. 32. Setup - Sensors - Sensor A - Label.

1.2.2.4. LABEL

(Sensor A or B input)

For a sensor already labeled, the display positions to and
highlights that label.

1. From the Sensor A selections, use the S and T

buttons to highlight LABEL.

2. Press the X button to display the label list.
3. Use the S and T buttons to scroll through the list

and highlight the desired label.
You may need to scroll up or down to view all possi-
ble labels.

4. Use the X button to accept the highlighted label

and exit the list.

NOTE: The label names in list order are: Sensor, Boiler,

Outdoor, Duct, Dischrg, Chiller, Room, Supply,
Return, and Animals.

ENTER

MINIMUM

VALUE FOR

SENSOR A

SETUP

SENSORS

SENSOR A

MIN VAL

0.0

F

o

M24592A

ENTER

MAXIMUM

VALUE FOR

SENSOR A

SETUP

SENSORS

SENSOR A

MAX VAL

0.0

F

o

SETUP

SENSORS

SENSOR

A

MIN

VAL

OR

MAX

VAL

SETUP
SENSORS

SENSOR

A

CALIBRATE

ENTER

VALUE TO

CALIBRATE

SENSOR A

SETUP

SENSORS

SENSOR A

CALIBRATE

0.0

F

o

M24594

SETUP
SENSORS
SENSOR

A

LABEL

SETUP

SENSORS

SENSOR A

LABEL

SELECT

LABEL FOR

SENSOR A

SENSOR A

BOILER A

OUTDOOR A

DUCT A

DISCHRG A

CHILLER A

ROOM A

M24595