T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER

62-0255—07

20

Fig. 42. Setup - Outputs - Mod Out - Reset.

1.3.1.6. RESET

This selection enables the controller’s Reset function, and
allows each output to be individually programmed for
Reset or No Reset.

IMPORTANT

To use the Reset function of the controller, the
first modulating output (MOD1) must be set for
Reset here.

The RESET choice is offered for all outputs in setup
mode, and you can set any or all of them for Reset=YES
or Reset=NO. The default is Reset=NO.

For the remaining outputs, if Reset=YES, then these
outputs use the reset curve programmed for the first
output.

1. From the Mod menu, use the S and T buttons to

highlight RESET.

2. Use the S and T buttons to highlight the desired

value.

Default: NO

3. Press the X button to accept the selection and

return to the Mod menu.

Fig. 43. Setup - Outputs - Mod 1/2- Hide.

1.3.1.7. Hide

The Hide option is used to prevent the MOD 1 and MOD 2
outputs from displaying on the Home screen.

1. From the Mod menu, use the S and T buttons to

highlight HIDE.

2. Use the S and T buttons to highlight YES or NO.

Default: YES

3. Press the X button to accept the selection and

return to the MOD menu.

NOTE: The MOD1 and MOD2 outputs are still active

even when hidden from the Home screen.

Fig. 44. Setup - Outputs - Mod Out - Exit.

1.3.1.7. Exit Modulating Outputs Setup

Press the W button (or highlight EXIT and press the X
button) to exit the Mod menu and return to the Outputs
menu.

To configure the second modulating output, go to “1.3.1.
Setting up the Modulating Outputs” on page 18.

When you finish setting up the two modulating outputs,
continue with “1.3.2. NBR OF RELAYS”.

SETUP
OUTPUTS

MOD 1

RESET

SETUP

OUTPUTS

MOD 1

RESET

USE

RESET

FOR

MOD1

YES-BOILER

YES-OTHER

NO

M24605

SETUP
OUTPUTS
MOD

1

HIDE

SETUP

OUTPUTS

MOD 1

HIDE

HIDE MOD 1 ON

HOME SCREEN

YES

NO

M28656

SETUP

OUTPUTS

MOD 1

TYPE

MIN OUT %

INTEGRAL

DERIVATIV

SCHEDULE

EXIT

M24606