T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER

27

62-0255—07

Fig. 63. Program - Action.

2.1.6. ACTION

1. From the menu, use the S and T buttons to high-

light ACTION.

Default: HEAT

2. Press the X button to display the action selections.
3. Use the S and T buttons to select the desired

value.

4. Press the X button to accept the highlighted selec-

tion and display the next option.

2.2. Program Next Output

(Modulating

Output or Relay)

For the next output, select the desired MOD or Relay from
the Program menu (see Fig. 57 on page 25).

Go to “2.1.2. SETPOINT” on page 25 to continue
programming.

When you finish programming the outputs, continue with
“1.3. Exit Programming without Reset”.

1.3. Exit Programming without Reset

Press the HOME button to leave programming mode and
return to the home screen.

This completes the programming procedure for
controllers that do not use Reset.

PROGRAM
MOD

1

ACTION

MENU

PROGRAM

MOD 1

ACTION

SELECT

ACTION

FOR

MOD 1

HEAT

COOL

REV ACT

DIR ACT

HUMID

DEHUMID

M24583