Exit sensor a setup, Sensor b (temperature only), Setting up the outputs – Honeywell T775U User Manual

Page 17

Advertising
background image

T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER

17

62-0255—07

Fig. 33. Setup - Sensors - Sensor A - Exit.

1.2.2.5. Exit Sensor A Setup

Press the W button to exit Sensor A selections and return
to the Sensors menu.
or
Use the S and T buttons to highlight EXIT and press the

X button.

Continue with “1.2.3. SENSOR B (Temperature only)”

Fig. 34. Setup - Sensors - Sensor B Menu.

1.2.3. SENSOR B (Temperature only)

For two-sensor reset control, Sensor B must always be
the controlling temperature. For example, in a reset
control based on outside temperature, Sensor B must be
the outside sensor.

NOTE: Sensor B is available only for reset on the

T775U2006, but can be controlled just like Sen-
sor A on the T775U2016.

1. From the Sensors menu, use the T button to high-

light SENSOR B.

2. Press the X button to display the Sensor B menu.
3. Repeat the selections described in “1.2.2. SENSOR

A” through “1.2.2.4. LABEL (Sensor A or B input)”
beginning on page 14, but perform only those steps
applicable to Sensor B.

4. Press the W button to exit SENSOR B and return to

the Sensors menu.
or
Use the S and T buttons to highlight EXIT and
press the X button.

5. Press the W button to exit the Sensors menu and

return to the Setup menu.

Continue with “1.3. Setting up the Outputs”.

Fig. 35. Setup - Outputs Menu.

1.3. Setting up the Outputs

1. From the Setup menu, use the Sand T buttons to

highlight OUTPUTS.

2. Press the X button to display the Outputs menu.

NOTE: The menus (e.g. the Outputs menu shown here)

can display only those relays that are defined in
Setup (see page 21). For example, if you config-
ure only two relays, then only two relays display
on the appropriate menus.

The following procedures set up each modulating output
and relay output.

SETUP

SENSORS

SENSOR A

UNITS

CALIBRATE

LABEL

EXIT

M24596

SETUP
SENSORS

SETUP

SENSORS

# SENSORS

SENSOR A

SENSOR B

EXIT

M24597

SETUP

OUTPUTS

MOD

1

SETUP

OUTPUTS

MOD 1

TYPE

MIN OUT %

INTEGRAL

DERIVATIV

SCHEDULE

RESET

HIDE

EXIT

M24599A